When there are not more than 30 current carrying conductors the derating factors for ampacities do not have to be applied.
Auxiliary gutters examples.
The capacities of bars cannot exceed 1 55 a per square millimeter 1000 a per square inch for copper and 1 09 a per mm2 700 a per square inch for aluminum.
This article covers the use installation and construction requirements of metal auxiliary gutters and nonmetallic auxiliary gutters and associated fittings.
Including the 1 0 awg conductor the metal wireway contains.
Below is a preview of article 376.
In auxiliary gutters and metal wireways it is not required to derate the ampacity of conductors if the number of current carrying conductors is 30 or less.
The sum of the cross sectional areas of all contained conductors at any cross section of an auxiliary gutter shall not exceed 20 of the interior cross sectional area of the gutter.
Sizing a gutter for the proper fit is relatively easy.
Figuring the 20 is easy for example.
A similar change occurred in article 366 for auxiliary gutters.
I get a lot of calls to make sure that the gutter that they are using is up to code.
The following refer to sheet metal auxiliary gutters.
Article 366 covers the use installation and construction requirements of auxiliary gutters and associated fittings.
Nonmetallic auxiliary gutters shall be per mitted to be installed outdoors where listed and.
Code quiz of day.
For example what is the maximum ampacity for a 1 0 awg thw copper conductor in a metal wireway under the following conditions.
There are two 4inch conduits feeding the bottom of the gutter with 4x600mcm conductors in parallel in each which pass straight through to the two 4inch nipples which connect to the bottom of the meter assembly feeding the 800 amp breaker.
Of its interior cross sectional area 366 22 a b this is for both sheet metal and nonmetallic gutters.
We are allowed by code to fill a gutter to 20.
Now when determining gutter or wireway fill the sum of the cross sectional areas of all contained conductors and cables at any cross section shall not exceed 20 percent of the interior cross sectional area of the wireway.